| Hose Specifications | Fire-Shield UL / ULC |
Tefcon UL / ULC |
||
|---|---|---|---|---|
| Hose Diameter (inches) | 1.5 | 2.0 | 1.5 | 2.0 |
| Number of Braids | 1 | 1 | 1 | 1 |
| Braid Alloy | Austenitic 300 series stainless steel | Austenitic 300 series stainless steel | Austenitic 300 series stainless steel | Austenitic 300 series stainless steel |
| Hose Material | Austenitic 300 series stainless steel | Austenitic 300 series stainless steel | PTFE Teflon | PTFE Teflon |
| Working Pressure (psi) [1] | 150/50 | 150/50 | 150 | 150 |
| Burst Pressure (psi) | 600 | 600 | 600 | 600 |
| Minimum Bend Radius (inches) [2] | 4.5 | 6.0 | 4.5 | 6.0 |
| Hex Fitting Type | S80 integral male or female (integral swivel optional) | S80 integral male or female (integral swivel optional) | S80 integral male or female (integral swivel optional) | S80 integral male or female (integral swivel optional) |
| Fitting Specifications | Fire-Shield | Tefcon | |||
|---|---|---|---|---|---|
| Fitting Size (inches) | Fitting Description | Thread Size (inches) [3] | Hex Size (inches) | Thread Size (inches) [3] | Hex Size (inches) |
| 3/4 | Male | 3/4 x 14 | 1.0625 | --- | --- |
| 1 | Male | 1 x 11-1/2 | 1.38 | --- | --- |
| 1-1/2 | Male | 1-1/2 x 11-1/2 | 1.94 | 1-1/2 x 11-1/2 | 2.00 |
| 2 | Male | 2 x 11-1/2 | 2.38 | 2 x 11-1/2 | 2.50 |
| 3 | Male | 3 x 8 | 4.00 | --- | --- |
| 2 | Female | 2 x 11-1/2 | 2.63 | 2 x 11-1/2 | 2.75 |
| 1-1/2 | Male Swivel | 1-1/2 x 11-1/2 | 1.94 | 1-1/2 x 11-1/2 | 2.00 |
| 2 | Male Swivel | 2 x 11-1/2 | 2.38 | 2 x 11-1/2 | 2.50 |
| 1-1/2 | Female Swivel | 1-1/2 x 11-1/2 | 1.94 | --- | --- |
| 2 | Female Swivel | 2 x 11-1/2 | 2.38 | 2 x 11-1/2 | 2.38 |
| 1-1/2 | Male Tee | 1-1/2 x 11-1/2 | 2.23 | --- | --- |
| 3 | Union | 3 x 8 | 5.75 | --- | --- |
Part Number: ACSWA
Hose Master's plated swivel adapter converts the integral hex male to a swivel end. This unique adapter creates a positive metal-to-metal seal when used with Hose Master's exclusive 30° chamfered hex male fitting. This swivel adapter facilitates installation and is only compatible with Hose Master's Fire-Shield or Tefcon connectors.
Part Number: ACANO
Hose Master's underground connectors, used with our anode, comply with EPA regulations for buried metal components. Our easily monitored system also meets NACE RP-01-69 standards for cathodic protection.